Number of counters: 1 to 2 – Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 34

Advertising
background image

26

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

Appendix 4 High Speed Counter – 2080-MOT-HSC

Number of Counters: 1 to 2

The module may be configured, using HSC_Mode, to use the inputs as 1 or 2
counters.
1 counter: A, B, Z = Counter 0
2 counters: A, Z = Counter0; B = Counter 1

Counter Pin Usage

125 Hz (DC 4 ms)

195 Hz (DC 2.6 ms)

131 Hz (DC 3.79 ms)

62.5 Hz (DC 8 ms)

97.3 Hz (DC 5.2 ms)

65.9 Hz (DC 7.6 ms)

31.25 Hz (DC 16 ms)

38.8 Hz (DC 10.3 ms)

32.9 Hz (DC 15.2 ms)

IMPORTANT

For low frequency pulses, filter times should be set appropriately to
avoid extra pulses from a noisy environment. For high frequency
pulses, shielded cable must always be used.

Nominal Filter Settings

Maximum Guaranteed
Block Pulse Width

Minimum Guaranteed Pass
Pulse Width

A

B

Z

Counter

HSC_Mode = 2 to 11

A

Z

Counter

HSC_Mode = 0, 1, 12, and 13

Counter

B

Input Operational Modes

Mode

Description

0

Up Counter – The accumulator is immediately cleared (0) when it reaches the high
preset. A low preset cannot be defined in this mode.

1

Up Counter with external reset and hold – The accumulator is immediately cleared (0)
when it reaches the high preset. A low preset cannot be defined in this mode.

2

Counter with external direction.

3

Counter with external direction, reset, and hold.

4

Two input counter (up and down).

5

Two input counter (up and down) with external reset and hold.

6

Quadrature counter (phased inputs A and B).

7

Quadrature counter (phased inputs A and B) with external reset and hold.

8

Quadrature X4 counter (phased inputs A and B).

9

Quadrature X4 counter (phased inputs A and B) with external reset and hold.

10

Quadrature X2 counter (phased inputs A and B).

Advertising