Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 71

Advertising
background image

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

63

Specifications Appendix A

Step Response to 63%

(1)

5 ms

Current Load ln voltage output, max

10 mA

Resistive load on current output

0…500

Ω (includes wire resistance)

Load range on voltage output

> 1k

Ω @ 10V DC

Max. inductive load
(current outputs)

0.01 mH

Max. capacitive load
(voltage outputs)

0.1 µF

Overall Accuracy

(2)

Voltage Terminal: ±1% full scale @ 25 °C
Current Terminal: ±1% full scale @ 25 °C

Non-linearity (in percent full scale)

± 0.1%

Repeatability

(3)

(in percent full scale)

± 0.1%

Output error over full temperature range,
-20…65°C (-4…149°F)

Voltage: ± 1.5%
Current: ± 2.0%

Open and short-circuit protection

Yes

Output overvoltage protection

Yes

Input group to bus isolation

No isolation

Channel to channel isolation

Non-isolation

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4…149 °F)

Temperature, non-operating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40...85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing

Operating altitude

2000 m

Cable length, max.

10 m

(1) Step response is the period of time between when the D/A converter was instructed to go from minimum to full

range until the device is at 63% of full range.

(2) Includes offset, gain, non-linearity and repeatability error terms.

(3) Repeatability is the ability of the output module to reproduce output readings when the same controller value is

applied to it consecutively, under the same conditions and in the same direction.

Output Specifications – 2080-OF2

Attribute

2080-OF2

Advertising