Power supply – Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 50

Advertising
background image

42

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

Appendix 5 DeviceNet Plug-in – 2080-DNET20

Power Supply

The plug-in module gets its power from the Micro800 backplane. However, the
DeviceNet interface is isolated from the Micro800 system. Therefore, network
power to operate the DeviceNet transceiver on the plug-in module is supplied by
an external DeviceNet power supply.

If using a single power supply in the network, calculate the total current
requirement of all devices in the network and add +10% for current surge.
Recommended power supply is 1606-XLSDNET4.

If two or more power supplies are connected to the Kwinklink lite media (trunk
cable) V+ should be broken between the two power supplies.

IMPORTANT

For most applications, Rockwell Automation recommends that you use
default node and baud rate settings. The DeviceNet scanner plug-in will
be at node 0 and the devices will be at nodes 1...20. The baud rate will
be at 500k baud and the maximum trunkline length will be 75 m
(KwikLink Lite).

Power Supply Cable Dropline Length

Dropline Length

Allowable Current

1.5 m (5 ft)

3 A

2 m (6 ft)

2 A

3 m (10 ft)

1.5 A

4.5 m (15 ft)

1 A

6 m (20 ft)

0.75 A

V-
Power Supply

V+

CAN_H
CAN_L

V-
V+

V+ broken between
power supplies

only one ground

V+
Power Supply

V-

Enclosure

TIP

Grounding the network
If grounding at only one location, it is recommended that you ground at the
center of the network.

Advertising