RA_DNET_LDX_TC_RTD

This UDFB is used to read input data from the Thermocouple/RTD module.

AO_Ch0

INPUT

WORD

Analog Output Channel 0 value.
This value is valid only if Module1 = '0X2'

AO_Ch0

INPUT

WORD

Analog Output Channel 1 value.
This value is valid only if Module1 = '0X2'

DO_Module2

INPUT

UINT

Output data for Expansion Module 1.

DO_Module3

INPUT

UINT

Output Data for Expansion Module 2.

FBENO

OUTPUT

BOOL

Function block enable output.
TRUE upon exit.

AI_CH0

OUTPUT

WORD

Analog Input Channel 0 value.
This value is valid only if Module1 = '4X0'

AI_CH1

OUTPUT

WORD

Analog Input Channel 1 value.
This value is valid only if Module1 = '4X0'

AI_CH2

OUTPUT

WORD

Analog Input Channel 2 value.
This value is valid only if Module1 = '4X0'

AI_CH3

OUTPUT

WORD

Analog Input Channel 3 Value.
This value is valid only if Module1 = '4X0'

StatusCH0_3

OUTPUT

WORD

Analog input channel 0…3 status

DI_Module2

OUTPUT

UINT

Digital Expansion Module 1 Input Data.
Applicable only if catalog is with digital inputs.

DI_Module3

OUTPUT

UINT

Digital Expansion Module 2 Input Data.
Applicable only if catalog is with digital inputs.

(1) Use only valid strings combinations as mentioned above. If Module1, Module2, Module3 physical I/O does not

match the physical I/O present in base and expansion, then incorrect sequence will be written.

RA_DNET_LDX_TC_RTD: Input and Output Parameters

Variable Name

Type

Data Type

Description

FBEN

INPUT

BOOL

Function block enable input.
TRUE to enable function.

SlotID

INPUT

UINT

Plug-in slot number (1…5)

NodeID

INPUT

USINT

Node address of the digital Compact I/O slave node.

FBENO

OUTPUT

BOOL

Function block enable output.

CH0

OUTPUT

WORD

RTD/Thermocouple input channel 0 value.

CH1

OUTPUT

WORD

RTD/Thermocouple input channel 1 value.

CH2

OUTPUT

WORD

RTD/Thermocouple input channel 2 value.

CH3

OUTPUT

WORD

RTD/Thermocouple input channel 3 value.

StatusCH0_3

OUTPUT

WORD

RTD/Thermocouple Input channel 0…3 status.

RA_DNET_LDX_ANALOG: Input and Output Parameters

Variable Name

Type

Data Type

Description

FBEN

SlotID

NodeID

FBENO

CH0

CH1

CH2

CH3

StatusCH0_3