Appendix A Specifications

AC on-state current, min

2.0 mA @ 9V AC (rms)

AC on-state current, max

5.0 mA

AC off-state voltage

3.5V AC (rms)

Output Specifications – 2080-OB4, 2080-OV4, 2080-IQ4OB4, 2080-IQ4OV4

Attribute

Value

Power supply voltage

10.8V DC, min
30V DC, max

On-state voltage

10V DC, min
24V DC, nom
30V DC, max

On-state current

5.0 mA @ 10V DC, min
0.5 A max, steady state
2 A surge, 2 s min

Environmental Specifications – 2080-OB4, 2080-OV4, 2080-IQ4OB4,
2080-IQ4OV4, 2080-IQ4

Attribute

Value

Temperature, operating

IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4…149 °F)

Temperature, surrounding
air, max.

65 °C (149 °F)

Temperature, non-operating

IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-40...85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
DIN rail mounting: 25 g
Panel mounting: 35 g

Shock, non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:
10 V/M with 1 kHz sine-wave 80%AM from 80…2000 MHz
10 V/M with 200 Hz 50% Pulse 100%AM @ 900 MHz
10 V/M with 200 Hz 50% Pulse 100%AM @1890 MHz
10 V/M with 1 kHz sine-wave 80%AM from 2000…2700 MHz

Input Specifications – 2080-IQ4, 2080-IQ4OV4, 2080-IQ4OB4