22

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

Appendix 3 Non-isolated Thermocouple and RTD Plug-in Modules – 2080-TC2 and 2080-RTD2

Connected Components
Workbench Global
Variables
Data Maps

The following bit/words describe the information read from the Thermocouple
and RTD plug-in modules in the Connected Components Workbench Global
Variables.

Mapping Table

Word Offset

Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

00 (example: _IO_P1_AI_00)

Channel 0 Temperature Data

01 (example: _IO_P1_AI_01)

Channel 1 Temperature Data

02 (example: _IO_P1_AI_02)

Channel 0 Information

UKT

UKR

Reserved

Reserved

OR

UR

OC

DI

CC

Reserved

03 (example: _IO_P1_AI_03)

Channel 1 Information

UKT

UKR

Reserved

Reserved

OR

UR

OC

DI

CC

Reserved

04 (example: _IO_P1_AI_04)

System Information

Reserved

SOR SUR

COC

CE

Reserved

Bit Definitions

Bit Name

Description

Channel Temperature Data

The temperature count mapped from temperature Celsius degree
with one decimal. Please check the section,

Temperature

Conversion – Data to Degree Celsius (°C) on page 23

, for the

mapping formula.

UKT (Unknown Type)

Bit set to report an unknown sensor type error in configuration.

UKR (Unknown Rate)

Bit set to report an unknown update rate error in configuration.

OR (Overrange)

Bit set to indicate overrange on channel input. The Channel
Temperature Data shows maximum temperature count for
individual type of sensor used and the value does not change
until overrange error is clear.

UR (Underrange)

Bit set to indicate the channel input underrange happens. The
Channel Temperature Data will show minimum temperature
count for individual type of sensor used and the value does not
change until underrange error is clear.

OC (Open Circuit)

Bit set to indicate open-circuit on the channel input sensor.

DI (Data Illegal)

The data in the channel data field is illegal and cannot be used
by user. This bit is set when temperature data is not ready for
use.

CC (Code Calibrated)

Bit set indicates temperature data is calibrated by the system
calibration coefficient.

SOR (System Overrange)

Bit set to indicate system overrange error with environment
temperature over 70 °C.

SUR (System Underrange)

Bit set to indicate system underrange error with environment
temperature under -20 °C.

COC (CJC open-circuit)

Bit set to indicate CJC sensor not connected for thermocouple
module, open circuit. This bit is for thermocouple module only.

CE (Calibration Error)

Bit set indicates that the module is not accurate. This bit is set to
0 by default and should remain as 0. Contact Technical Support
when the value is otherwise.