Z input (gate) function/touch probe, Ring or linear counter – Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 39

Advertising
background image

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

31

High Speed Counter – 2080-MOT-HSC Appendix 4

Down Counting

Z Input (Gate) Function/Touch Probe

This signal functionality supports:

Touch Probe the present count value on the rising edge of IntZ_n to the

HSC_Touch Probe term in the backplane input file.

Hold the counter at its present count value while IntZ_n = 1,
Reset the present count value on rising edge of IntZ_n.

Ring or Linear Counter

The counter may be configured with the RingOrLinearCnt_n control bit to
rollover at its limits (ring counter) or to stop counting and set a flag (linear
counter).

0: ring counter.

When the counter is a ring counter and the present count value

is equal to MaxCountValue_n, the next input count in the up direction will cause
the PresentCount_n to become the MinCountValue_n. This action is known as
rollover. And the CountOverflow_n flag will be set to indicate that a rollover has
happened. It is reset using the ResetCountOverflow bit.

Conversely, when the PresentCount_n is equal to MinCountValue_n the next
input count in the down direction will cause the PresentCount_n to become the
MaxCountValue_n. This action is known as rollunder. The CountUnderflow_n

INPUT A

INPUT B

INPUT Z

Decrement Pulse
(count down)

Decrement Pulse
(count down)

Encoder or Sensor

Encoder or Sensor

-1

-2

-3

-4

-5

-6

-7

-8

-1

-2

-3

-4

-5

-6

-7

-8

Counter 0

(Input A)

PresentCount 1

Counter 0

(Input B)

PresentCount 2

IMPORTANT

If the module gets two or more Z pulses during a single plug-in scan the
HSC_TouchProbe will be overwritten with the last stored value. There
will be no indication that more than one store has occurred.