5 - devicenet plug-in – 2080-dnet20, Devicenet plug-in – 2080-dnet20, Overview – Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 47: Status indicators, Chapter 5, Overview status indicators, Chapter

Advertising
background image

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

39

Chapter

5

DeviceNet Plug-in – 2080-DNET20

Overview

The DeviceNet plug-in serves as scanner and client for explicit messaging to
remote devices. The module is designed to scan devices such as:

• CompactBlock™ LDX
• PowerFlex® drives
• E1Plus overloads
• stack lights

User-defined function blocks (UDFB) are required to enable interaction
between these devices.

The 2080-DNET20 DeviceNet scanner supports a maximum of 20 nodes. For
example, if the scanner ID is configured to zero, the scanner would scan from
1…20. It is supported on Micro800 controllers with available plug-in slots. Only
one 2080-DNET20 DeviceNet scanner is supported per controller.

Status Indicators

The DeviceNet plug-in module supports two standard DeviceNet green and red
LED indicators:

• Module status
• Network status

IMPORTANT

Rockwell Automation recommends that only one 2080-DNET20
DeviceNet scanner be used for one network.

Module Status Indicator

LED state

Module status

Description

OFF

No power

There is no power present.

Flashing Green

Operational

Unit is starting up.

Green

Unit operational

Device is operating normally.

Flashing Red

Minor fault.

A recoverable fault is present or the module is
undergoing firmware update.

Red

Unrecoverable fault.

A non-recoverable fault is detected.

Network Status Indicator

LED state

Module Status

Description

OFF

No power or offline

There is no network power or device is not operating.

Flashing Green

Idle

No valid network connection has been made.

Advertising