Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 69

Advertising
background image

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

61

Specifications Appendix A

Shock, non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
DIN rail mounting: 25 g
Panel mounting: 35 g

ESD Immunity

IEC 61000-4-2:
6kV contact
8 kV air

Radiated RF immunity

IEC 61000-4-3
10 V/M with 1 kHz sine-wave 80%AM from 80…2000 MHz
10 V/M with 200 Hz sine-wave 50% Pulse 100%AM @ 900 MHz
10 V/M with 200 Hz sine-wave 50% Pulse 100%AM @1890 MHz
10 V/M with 1 kHz sine-wave 80%AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:
±2 kV @ 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

Certifications – 2080-OW4I

Certification (when
product is marked)

(1)

(1) See the Product Certification link at

http://www.rockwellautomation.com/products/certification/

for

Declarations of Conformity, Certificates, and other certification details.

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada.

See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,

certified for U.S. and Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with:EN 61131-2;

Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications

Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3

Environmental Specifications – 2080-OW4I

Attribute

Value