DeviceNet Plug-in – 2080-DNET20 Appendix 5

DeviceNet Switches

2080-DNET20 Assembly Diagram

ON

1

2

3

4

5

7

6

8

Dim A

Pos. 1 Designate

Pin #1 Location

1

3

5

7

9

11

13

15

2

4

6

8

10

12

14

16

CONTACT CONFIGURATION

(Pos. 1 denotes Pin # 1)

DeviceNet Address (MAC_ID) Switch Definitions

Node Address

SW1 Switch Positions

3

4

5

6

7

8

Switch Position Values

32

16

8

4

2

1

0 (default)

OFF

OFF

OFF

OFF

OFF

OFF

1

OFF

OFF

OFF

OFF

OFF

ON

2

OFF

OFF

OFF

OFF

ON

OFF

3

OFF

OFF

OFF

OFF

ON

ON

4

OFF

OFF

OFF

ON

OFF

OFF

5

OFF

OFF

OFF

ON

OFF

ON

62

ON

ON

ON

ON

ON

OFF

63

ON

ON

ON

ON

ON

ON

DeviceNet Baud Rate Switch Definitions

Baud Rate DR (Data Rate) SW1 Switch Position

1

2

125k

OFF

OFF

250k

OFF

ON

500k (default)

ON

OFF

Autobaud

ON

ON