Configuring Communications

3-7

Configuring the RS-232 Serial to KF/KE/CH0 (DH+)

For information on the configuration characteristics for RS-232 to KF/KE/Ch0

(DH+), see Table 3.D.

Table 3.D

Configuration Characteristics for RS-232 Serial to KF/KE/CH0 (DH+)

If you want to:

Press this key:

Assign a unique communication device name (1-8 characters). This

field must be defined for the software to accept the configuration.

You cannot modify this field. The communication device name that

you assign will appear on the screen when you use WHO.

F1

Device Name

Assign a description for a communication device (1-50 characters).

You must define this field for the software to accept the configuration.

F2

Enter Device Description

Select the RS-232 Serial to KF/KE/CH0 (DH+) option.

F3

Select Interface Hardware

Assign a timeout for processor reply. Available choices are: 15, 20,

25, 30, 35, 40, 45, 50, 55 and 60 seconds. The default is

20 seconds.

F4

Online Wait for Reply

Assign a communication port. Toggle through COM1, COM2, and

user specified. If you choose the user-specified port, you must enter

the serial port I/O address and the interrupt (IRQ).

F5

Communications Port

Define a communication rate to send information. Toggle through

300, 600, 1200, 2400, 4800, 9600 and 19200 baud rates. The

default is 19200 baud.

F6

Baud Rate

Choose the method of error checking your computer will support.

Toggle between even and none. The default is none.

F7

Parity

Set error detection. Toggle between:
·BCC

The computer sends and accepts messages that end

with a BCC byte for error checking.

·CRC

The computer sends and accepts messages with a

2-byte CRC for error checking.

The default is BCC.

F8

Error Checking Mode

Choose the serial protocol. Toggle between Half Duplex and Full

Duplex. The default is Full Duplex.

F9

Serial Protocol

Enter the source station address (1-9 characters)

Ctrl

F1

Computer Station Address