Mounting the Drive
Mount the drive on a flat, vertical, and level surface. The drive must be mounted
vertically (top up) for proper heat dissipation. Refer to Appendix A for drive mounting
dimensions.
Install the drive with four (4) M4 x .07 (8-32) screws. Torque the mounting screws to
1.2 Nm (11 lb/in).
Ensure that debris cover is in place when installing the drive to prevent filings, cable
insulation and dust from entering the drive.