English – Rockwell Automation SP120 ACDrive 115VAC, 1Ph, 230VAC, 1Ph/3Ph, 1/4-5.0HP User Manual

Page 46

Advertising
background image

3-16

SP120 AC Drive Installation and Operation

English

3.2.4 b Group – Advanced Control and Protection Parameters

Tunable parameters are indicated with an asterisk ( * ) precediing the parameter
number.

Parameter

Number

Parameter Name/Description

Min./Max

Range

Units

Factory

Default

Automatic Start After a Fault
b01

Restart Mode Select
Selects the restart mode for the drive
Settings: 00=Fault indication
01=0 Hz start
02=Synchronize.
03=Synchr. and stop
Note: If set to 01, 02 or 03 the drive will attempt to
restart the following number of times after the following
events:
Overcurrent – 3 restarts
Overvoltage – 3 restarts
Undervoltage – 16 restarts (refer to b03
[

RESTART

TIME

] for time between restart

attempts)

00 to 03

Numeric
Value

00

!

ATTENTION: This parameter may only be
used as outlined in NFPA 79, Under Voltage
Protection." Failure to observe this
precaution could result in bodily injury.

b02

Power Loss Time
If undervoltage exists longer than the programmed time,
the drive will fault even if b01 [

RESTART

MODE

SELECT

] is

active.

0.3 to 25.0

0.1
seconds

1.0

b03

Restart Time
Sets the time between restart attempts after an
undervoltage fault or the removal of a digital input set to
11 {FRS}.

0.3 to 100.0

0.1
seconds

1.0

Electronic Motor Protection
b12

Motor Overload Current
Set to motor nameplate full load amps.

5 to 120% of
rated current

0.01 A

115% of drive

rating

b13

Motor Overload Select
Selects the characteristics of the electronic thermal
protection.
Settings: 00 = Derating 1
01 = No Derating
02 = Derating 2

00 to 01

Numeric
Value

01

80%

20Hz

Torque

5Hz

100%

Output frequency

b13 = 01

120Hz

60%

60Hz

b13 = 00

b13 = 02