Installing and Wiring the Drive
2-15
English
27
{UP}
Remote Control
UP
These settings allow digital inputs to increase and decrease the
commanded frequency for the drive. Parameter A01 [
FREQUENCY
COMMAND
SELECT
] must be set to 02 to activate this function. These
inputs will change the value of parameter F01 [
FREQUENCY
COMMAND
] in
Hz/sec as defined by parameter A04 [
MAXIMUM
FREQUENCY
] ÷ (Accel
time or Decel time).
28
{DWN} Remote Control
DOWN
31
{OPE}
Run Command
Source Select
This setting is used to determine the source of the Run commands.
Table 2.5 – Programmable Digital Input Functions
Numeric
Setting
Alpha
Setting
Function
Description
RUN (NO)
27 {UP} (NO)
28 {DWN} (NO)
PF01-
[Freq. Command]
Motor Speed
Inactive
Active
Start command will come from the control terminals only,
regardless of the setting of PA02 - [Start Command Select]
Start command will come from the start key on the keypad only
regardless of the setting of PA02 - [Start Command Select]