{UP}

Remote Control
UP

These settings allow digital inputs to increase and decrease the
commanded frequency for the drive. Parameter A01 [

FREQUENCY

COMMAND

SELECT

] must be set to 02 to activate this function. These

inputs will change the value of parameter F01 [

FREQUENCY

COMMAND

] in

Hz/sec as defined by parameter A04 [

MAXIMUM

FREQUENCY

] ÷ (Accel

time or Decel time).

28

{DWN} Remote Control

DOWN

31

{OPE}

Run Command
Source Select

This setting is used to determine the source of the Run commands.

Table 2.5 – Programmable Digital Input Functions

Numeric

Setting

Alpha

Setting

Function

Description

RUN (NO)

27 {UP} (NO)

28 {DWN} (NO)

PF01-
[Freq. Command]

Motor Speed

Inactive

Active

Start command will come from the control terminals only,
regardless of the setting of PA02 - [Start Command Select]

Start command will come from the start key on the keypad only
regardless of the setting of PA02 - [Start Command Select]