English – Rockwell Automation SP120 ACDrive 115VAC, 1Ph, 230VAC, 1Ph/3Ph, 1/4-5.0HP User Manual

Page 23

Advertising
background image

Installing and Wiring the Drive

2-9

English

H

10 V Reference Voltage for
Analog Frequency
Command

Input OI for 4-20 mA is activated when one of the digital inputs
is set to 16{AT} via parameters C01 [

DIGITAL

INPUT

1] to C05

[

DIGITAL

INPUT

5].

The analog input reference can be adjusted using parameters
A11 [

ANALOG

FREQUENCY

MINIMUM

] to A16 [

ANALOG

FILTER

SELECT

].

If no digital input is programmed as 16{AT}, the set values are
the sum of O and OI.

O

Voltage Analog Input
Frequency Command
(0-10 V)

OI

Current Analog Input
Frequency Command
(4-20 mA)

L

0 V Reference Potential for
Frequency Comand Inputs

FM

Programmable Analog
Output

Analog or Pulse Output
Frequency or Motor Current

This output can be used to monitor the output frequency of the
drive (either Analog or Pulse) or the motor current. This output
is programmable using parameter C23 [

OUTPUT

FM

].

Analog Signal: The relation t/T (duty cycle) changes
proportionally with the frequency or current. The maximum
voltage of 10V (100% duty cycle) is reached when the
maximum frequency or 200% of the rated current is reached.
Parameter b81 [

OUTPUT

FM

FACTOR

] may be used as a scaling

factor.
Accuracy: +/- 5% for frequency , +/- 20% for current

Pulse Signal: Frequency = output frequency x b86 [

PROCESS

DISPLAY

SCALE

FACTOR

], but the maximum frequency is 3.6 kHz

(ex. Freq = 60Hz x 60 = 3.6kHz).

Table 2.4 – Control Terminal and Fault Relay Terminal Descriptions

Control

Terminal

Function

Description

Potentiometer
1 to 2 kOhm

Input impedance
10 kOhm

Input impedance
250 Ohm

H

O

OI

L

H

O

OI

L

H

O

OI

L

+

-

4-19.6 mA

0-9.6 V

+

PE

PE

PE

nominal 0-10 V

nominal 0-20 mA

Analog Signal
Frequency or Current

Pulse Signal (50% duty cycle)
Frequency only

T = 4 ms (constant)

T = (Variable)