3-18

SP120 AC Drive Installation and Operation

English

Parameter

Number

Parameter Name/Description

Min./Max

Range

Units

Factory

Default

Initialization / Adjustment Function (continued)
b84

Reset Functions
Resets the factory defaults or clears the fault history.
Settings: 00=Clear fault history
01=Reset defaults
Note: To activate this parameter, set the value and
press Enter, then hold the PROGram, Up Arrow, Down
Arrow, and Stop for 3 seconds, release only Stop until
the display is blinking, then release all of the keys.
Note: Defaults will reset to factory settings determined
by b85 [

FACTORY

DEFAULTS

SELECT

]

00 to 01

Numeric
Value

01

b85

Factory Defaults Select
Selects which set of defaults to use.
Settings: 06=Previous K version (50 Hz, Europe only)
07=U version (60 Hz)
Note: Settings 00 – 05 are not used.

01 to 07

Numeric
Value

07

*b86

Process Display Scale Factor
Sets the frequency factor for d07 [

PROCESS

DISPLAY

].

Also sets the multiplier that is applied to the output
frequency for the FM pulse signal.
This parameter can be changed while motor is running

0.1 to 99.9

N/A

30.0

b87

STOP Key Select
This parameter is not active when b85 [

FACTORY

DEFAULTS

SELECT

] is set to 06 or 07.

00/01

Numeric
Value

00

b88

FRS Select
Selects the operation of the drive after a digital input
(C01 – C05) setting 11{FRS} input is removed.
Settings: 00=0 Hz start
01=Synchronization of motor speed after
waiting period programmed via b03 [

RESTART

TIME

].

00 to 01

Numeric
Value

00

b89

Keypad Display
Selects the display parameter that will be shown on the
fixed keypad when the remote keypad is connected.
Settings: 01 = d01 [

OUTPUT

FREQUENCY

]

02 = d02 [

OUTPUT

CURRENT

]

03 = d03 [

DIRECTION

OF

ROTATION

]

04 = d04 [

PID

PROCESS

DISPLAY

]

05 = d05 [

DIGITAL

INPUT

STATUS

]

06 = d06 [

OUTPUT

STATUS

]

07 = d07 [

PROCESS

DISPLAY

]

01 to 07

Numeric
Value

01

b92

(Reserved)
Reserved for future use. DO NOT CHANGE

00/01

00

!

ATTENTION: If parameter b85 settings
00 through 05 are activated, this
parameter will control the operation of
the keypad STOP key. Setting 00 will
enable the STOP key and 01 will disable
the STOP key. Disabling the STOP key
is not recommended as it could result in
personal injury, loss of life, or equipment
damage.