Setting Drive Control to the Keypad

This example shows you how to configure the drive for keypad control. You will need to
change the values of three parameters to accomplish this.

Step 1. Program A01 [

FREQUENCY

COMMAND

SELECT

] to change the frequency

reference command from the control terminal block (factory default) to the
speed potentiometer on the keypad.

Step 2. Program A02 [

START

COMMAND

SELECT

] to change the source of the start

input from the control terminal block (factory default) to Start on the keypad.

Step 3. Program C13 [

DIGITAL

INPUT

3

LOGIC

] to change the input from a normally

closed contact (NC) to a normally open contact (NO).

Step 4. Verify that F04 [

START

KEY

DIRECTION

] is not set to 2 (Control Terminal).

Step 5. Verify that C1 through C5 [

DIGITAL

INPUTS

1-5] are at default values.

Action

Description

Display

Press PROGram to switch from the parameter value to the parameter number.

d01

Press Up Arrow or Down Arrow to scroll through the parameter groups stopping at
the A group.

A--

Press PROGram to enter into the A group.

A01

If a parameter other than A01 [

FREQUENCY

COMMAND

SELECT

] is displayed press

Down Arrow until A01 is displayed.

00

Press PROGram to view the parameter value.

01

Use Down Arrow to change the value of A01 from the default value of 01 to 00.
This changes the source of the frequency command to the potentiometer on the
fixed keypad.

00

When the desired value is displayed, press the Enter Key. This writes the new
value to memory. The display will return to the parameter number.

A01

Press Up Arrow to display A02 [

START

COMMAND

SELECT

].

A02

Press PROGram to view the parameter value stored in A02.

01

Use Up Arrow to change the value of A02 from the default value of 01 to 02. This
changes the source of the start input from the control terminal block to the fixed
keypad.

02

When the desired value is displayed, press Enter. This writes the new value to
memory. The display will return to the parameter number.

A02

Press Down Arrow until C13 [

DIGITAL

INPUT

3

LOGIC

] is displayed.

C13

Press PROGram to view the parameter value.

01

Use Down Arrow to change the value of C13 from the default value of 01 to 00.
This changes the input to a normally open contact.

00

When the desired value is displayed, press the Enter Key. This writes the new
value to memory. The display will return to the parameter number.

C13

PROG

PROG

PROG

PROG