Parameters and Programming

3-13

English

Parameter

Number

Parameter Name/ Description

Min./Max

Range

Units

Factory

Default

DC Brake

A51

DC Brake Enable
Used to enable/disable DC injection braking
Settings: 00=Disabled
01=Enabled

00 to 01

Numeric
Value

00

A52

DC Brake Start Frequency
Sets the frequency at which the DC brake will become
active.

0.5 to 10.0

0.1 Hz

10.0

A53

DC Brake Wait Time
Sets the time the drive will wait after A52 [

DC

BRAKE

START

FREQUENCY

] before applying A54 [

DC

HOLD

VOLTAGE

].

0.0 to 5.0

0.1 sec

0.0

A54

DC Hold Voltage
Sets the level of DC braking voltage in percent of A82
[

BASE

VOLTAGE

].

0 to 100

1% of drive
rating

0

A55

DC Hold Time
The time that A54 [

DC

HOLD

VOLTAGE

] is applied to the

motor after A53 [

DC

BRAKE

WAITING

TIME

] has expired.

0.0 to 60.0

0.1 sec

0.0

Operating Frequency Range

A61

Upper Frequency Limit
This is an upper frequency limit similar to A04 [

MAXIMUM

FREQUENCY

] except that it can be set lower than A03

[

BASE

FREQUENCY

]. A value of 0.0 will disable this

parameter.

Output Frequency

0.5 to 360.0

0.1Hz

0.0

A62

Minimum Frequency
Lowest frequency the drive will output continuously.
Refer to diagram in A61 [

UPPER

FREQUENCY

LIMIT

].

0.0 to 360.0

0.1Hz

0.0

A63

Skip Frequency 1
Sets a frequency at which the drive will not output
continuously.

0.0 to 360.0

0.1Hz

0.0

A64

Skip Frequency Band 1
Sets the bandwidth around A63 [

SKIP

FREQUENCY

1].

The bandwidth is 2x A64 [

SKIP

FREQUENCY

BAND

1] with

½ the band below and ½ the band above A63 [

SKIP

FREQUENCY

1].

0.0 to 10.0

0.1Hz

0.5

A65

Skip Frequency 2
Sets a frequency at which the drive will not output
continuously.

0.0 to 360.0

0.1Hz

0.0

A61

Frequency Command

A62