3-10

SP120 AC Drive Installation and Operation

English

Parameter

Number

Parameter Name/ Description

Min./Max

Range

Units

Factory

Default

Analog input reference adjustment (continued)

A13

Analog Input Minimum
Sets the starting point (offset) for the analog input
range. Refer to diagram in A11 [

ANALOG

FREQUENCY

MINIMUM

]

0 to 99

1%

0

A14

Analog Input Maximum
The ending point (offset) for the analog input range.
Refer to diagram in A11 [

ANALOG

FREQUENCY

MINIMUM

]

0 to 100

1%

100

A15

Analog Start Select
Sets the output frequency when frequency reference is
below value set in A13 [

ANALOG

INPUT

MINIMUM

].

Settings: 00 = A11 [

ANALOG

FREQUENCY

MINIMUM

]

01 = 0 Hz

00 to 01

Numeric
Value

01

A16

Analog Filter Select
Sets the level of the Analog input smoothing filter where:
1 = low (Bandwidth = 200 Hz)
8 = high (Bandwidth = 25 Hz).

1 to 8

Numeric
Value

8

Preset Frequencies

*A20

Internal Frequency
When A01 [

FREQUENCY

COMMAND

SELECT

] is set to 02,

this parameter will provide the drives frequency
command. This parameter will change the frequency
command only after the new frequency is entered into
memory.

This value can also be changed via F01 [

FREQUENCY

COMMAND

] if no preset frequency inputs are active.

This parameter can be changed while motor is running.

0.0 to 360.0

0.1 Hz

60.0

A12

A13

0V
4mA

A14

10V
20mA

% Input
Scale

Frequency

A11

A15=01

A15=00