Parameters and Programming

3-7

English

3.2

Parameter Descriptions

The sections that follow provide descriptions of all drive parameters, separated by
group.

3.2.1 D Group - Display and Diagnostic Parameters (Read Only)

This group of parameters consists of commonly viewed drive operation conditions
such as output frequency. All parameters in this group are Read Only.

Parameter

Number

Parameter Name / Description

Min./Max.

Range

Units

d01

Output Frequency
Displays the output frequency to the motor.

0.0 to 360.0

N/A

d02

Output Current
Displays the output current to the motor.

0.00 to 999.9

0.01 A

d03

Direction
Displays the present direction of rotation.

F=Forward
r=Reverse
o=Stop

N/A

d04

PID Process Display
Displays the scaled PID Process variable (feedback). Available only
when the PID control is active. The scale factor is set using A75
[

PROCESS

REFERENCE

SCALE

FACTOR

].

0.00 to 100.0

0.01%

d05

Digital Input Status
Displays the status of the 5 digital inputs regardless of how each input
is programmed in C11 [

DIGITAL

INPUT

1

LOGIC

] through C33 [

ALARM

RELAY

AL

1

LOGIC

].

5 4 3 2 1

N/A

N/A

d06

Output Status
Displays the status of the digital outputs and the fault indication
relays.

AL 12 11

N/A

N/A

d07

Process Display
Displays d01 [

OUTPUT

FREQUENCY

] scaled by the variable set in b86

[

PROCESS

DISPLAY

SCALE

FACTOR

].

Note: If there are more than 4 digits, the LSB will be dropped.

0.00 to 9990

0.01

d08

Last Fault
Displays the last fault. The output frequency, motor current, and DC
bus voltage at the time of the last fault can be viewed by pressing
PROGram. If there has not been a fault or the register has been
cleared, then --- will be displayed.

N/A

N/A

High
Open

High
Open