SP120 AC Drive Installation and Operation

English

CM2

Reference potential for
outputs 11 and 12

Transistor output, max. 27 Vdc, 50 mA

The outputs can be programmed as either NO (active high) or
NC (active open) contacts using parameter C31 [

DIGITAL

OUTPUT

11

LOGIC

] and C32 [

DIGITAL

OUTPUT

12

LOGIC

].

The following 6 settings may be programmed using parameter
C21 [

DIGITAL

OUTPUT

11] and C22 [

DIGITAL

OUTPUT

12]:

00{RUN} = Motor Running (Signal if output frequency > 0.5 Hz)
01{FA1} = At frequency (Signal when the set frequency is

reached and that frequency is > 0.5Hz)

02{FA2} = Above frequency (Signal if output frequencies > the

frequencies set under parameter C42 [

ABOVE

FREQUENCY

ACCEL

SETTING

] or C43 [

ABOVE

FREQUENCY

DECEL

SETTING

] and > 0.5 Hz).

03{OL} = Motor overload (Signal if the motor current exceeds

the value set under C41 [

OVERLOAD

ALARM

SETTING

]

04{OD} = PID-deviation (Signal if the deviation between the set

value and the actual value returned is greater than the
value set under C44 [

PID

DEVIATION

SETTING

]). Only

available if the PID control A71 [

PID

ENABLE

] is active.

05{AL} = Fault (Signal if a fault is indicated)

12

Programmable Digital Output

11

Programmable Digital Output

AL0

Fault Relay

Parameter C33 [

FAULT

RELAY

AL

1

LOGIC

] can be used to invert

the operation.

The fault relay is set with a time delay of approximately 2 sec
after the power is switched on.

AL1

AL2

Table 2.4 – Control Terminal and Fault Relay Terminal Descriptions

Control

Terminal

Function

Description

AL0

AL1

AL2

230VAC

250 VAC, 2.5 A resistive
0.2A inductive

30 VDC, 3.0A resistive
0.7A inductive

min. 100 VAC, 10mA
5 VDC 100 mA

Faulted / De-energized State

C33

C33 = 01

C33 = 00

AL0 - AL1 Open when Faulted

Open when Power Off

Closed when Faulted
Open when Power Off

AL0 - AL2 Closed when Faulted

Closed when Power Off

Open when Faulted
Closed when Power Off