Figure 2.7 and table 2.4 provide descriptions of the drive control terminals and fault
relay terminals.

Figure 2.7 – Control Terminal Block and Fault Relay Terminal Block

!

ATTENTION: Do not jumper or short circuit terminals H and L or P24
and L. Failure to observe this precaution could result in damage to, or
destruction of, the equipment.

L 5

4

3

2

1 P24

Control Terminal Block

H

O 0I

L FM CM2 12 11

Control Terminal Block

AL0

Fault relay

terminal block

AL1 AL2

Fault Relay
Terminal Block

Table 2.4 – Control Terminal and Fault Relay Terminal Descriptions

Control

Terminal

Function

Description

P24

24 V DC

24 V potential or digital inputs 1-5, max. load 30 mA

1

Programmable Digital Inputs.
26 V max, 5 K

input

impedance.

Digital inputs 1 – 5 are fully programmable level triggered
inputs. An overview of the possible functions can be found in
the digital input description table in section 2.6
The inputs are fully programmable with these exceptions:

No two inputs can have the same function

Only input 5 can be programmed as PTC.

With the exception of the reset setting, which must be NO
(active high), all of the inputs can be set as NO (active high) or
NC (active open) via parameters C11 [

DIGITAL

INPUT

1

LOGIC

] to

C15 [

DIGITAL

INPUT

5

LOGIC

].

Note: A signal must be applied to the digital inputs for at least

12 msec in order to be read by the drive.

2

3

4

5

L

0 V

0 V potential for output FM