English – Rockwell Automation SP120 ACDrive 115VAC, 1Ph, 230VAC, 1Ph/3Ph, 1/4-5.0HP User Manual
Page 22
![background image](/manuals/581255/22/background.png)
2-8
SP120 AC Drive Installation and Operation
English
Figure 2.7 and table 2.4 provide descriptions of the drive control terminals and fault
relay terminals.
Figure 2.7 – Control Terminal Block and Fault Relay Terminal Block
!
ATTENTION: Do not jumper or short circuit terminals H and L or P24
and L. Failure to observe this precaution could result in damage to, or
destruction of, the equipment.
L 5
4
3
2
1 P24
Control Terminal Block
H
O 0I
L FM CM2 12 11
Control Terminal Block
AL0
Fault relay
terminal block
AL1 AL2
Fault Relay
Terminal Block
Table 2.4 – Control Terminal and Fault Relay Terminal Descriptions
Control
Terminal
Function
Description
P24
24 V DC
24 V potential or digital inputs 1-5, max. load 30 mA
1
Programmable Digital Inputs.
26 V max, 5 K
Ω
input
impedance.
Digital inputs 1 – 5 are fully programmable level triggered
inputs. An overview of the possible functions can be found in
the digital input description table in section 2.6
The inputs are fully programmable with these exceptions:
•
No two inputs can have the same function
•
Only input 5 can be programmed as PTC.
With the exception of the reset setting, which must be NO
(active high), all of the inputs can be set as NO (active high) or
NC (active open) via parameters C11 [
DIGITAL
INPUT
1
LOGIC
] to
C15 [
DIGITAL
INPUT
5
LOGIC
].
Note: A signal must be applied to the digital inputs for at least
12 msec in order to be read by the drive.
2
3
4
5
L
0 V
0 V potential for output FM