English – Rockwell Automation SP120 ACDrive 115VAC, 1Ph, 230VAC, 1Ph/3Ph, 1/4-5.0HP User Manual

Page 50

Advertising
background image

3-20

SP120 AC Drive Installation and Operation

English

Parameter

Number

Parameter Name/Description

Min./Max

Range

Units

Factory

Default

Digital Inputs 1 – 5 (continued)
C11

Digital Inputs 1-5 Logic
Sets the digital inputs to be NO or NC contacts
Settings: 00=NO contact (active high)
01=NC contact (active open)

00 to 01

Numeric
Value

00

C12

00

C13

01

C14

00

C15

01

Outputs 11, 12, FM, AL0-AL1

C21

Digital Outputs 11-12
Sets the operation of the digital outputs
Settings: 00={RUN} (Motor running above 0.5 Hz)
01={FA1} (At frequency and above 0.5 Hz)
02={FA2} (Above frequency)
03={OL} (Overload alarm)
04={OD} (PID deviation)
05={AL} (Fault)
Refer to control terminal table in chapter 2 for setting
descriptions.

00 to 05

Numeric
Value

01

C22

00

C23

Output FM Select
Sets the operation of the output FM.
Settings: 00={A-F} (Analog Output Frequency)
01={A} (Motor Current)
02={D-F} (Digital Output Frequency)
Refer to control inputs table in chapter 2 for setting
descriptions.

00 to 02

Numeric
Value

00

C31

Digital Output 11-12 Logic
Sets the digital outputs to be NO or NC contacts.
Settings: 00=NO contact (Active high)
01=NC contact (Active open)

00 to 01

Numeric
Value

00
00

C32

C33

Fault Relay AL1 Logic
Sets the fault relay to be either NO or NC contacts.
Settings: 00 = NO contact (active high)
01 = NC contact (active open)
Refer to control inputs table in chapter 2 for setting
descriptions.

00 to 01

Numeric
Value

01

C41

Overload Alarm Threshold
Sets the allowable overload level before digital outputs
11-12 change state when set to 03 {0L}.

0 to 200% of
drive rating

0.01 A

100% of

drive rating

C42

Above Frequency Accel Threshold
Sets the frequency at which digital outputs 11-12
change state when set to 02 {FA2} if the drive is
accelerating.

0.0 to 360.0

0.1 Hz

0.0

C43

Above Frequency Decel Threshold
Sets the frequency at which digital outputs 11-12
change state when set to 02 {FA2} if the drive is
decelerating.

0.0 to 360.0

0.1 Hz

0.0

C44

PID Deviation Threshold
Sets the allowable PID Loop error before digital outputs
11-12 change state when set to 04 {OD}.

0.0 to 100% +/- 0.1%

+/-3.0