3-12

SP120 AC Drive Installation and Operation

English

Parameter

Number

Parameter Name/ Description

Min./Max

Range

Units

Factory

Default

V/F Characteristics / Boost

A41

Boost Select
Used to select auto or manual boost
Settings: 00=Manual Boost
01=Auto Boost

00 to 01

Numeric
Value

00

*A42

Manual Boost Voltage
Sets the boost level as a percent of A82 [

BASE

VOLTAGE

].

This parameter can be changed while motor is running.

0 to 99

1% of base
voltage

25

*A43

Manual Boost Frequency
Sets the boost frequency point as a percent of A03
[

BASE

FREQUENCY

]. Refer to diagram in A42 [

MANUAL

BOOST

VOLTAGE

]

This parameter can be changed while motor is running.

0.0 to 50.0% 0.1%

2.0

A44

V/Hz Select
Used to select the V/Hz mode.
Settings: 00=Constant Torque
01=Variable Torque

00 to 01

Numeric
Value

00

*A45

Maximum Voltage Gain
Sets the voltage gain of the V/Hz characteristic. Value is
a percent of A82 [

BASE

VOLTAGE

].

This parameter can be changed while motor is running.

20 to 100

1%

100

A42

30Hz

Voltage

A43

100%

60 Hz

Frequency

99 ~ 20%
of Base Voltage at 0Hz
then linear scale down
e.g. 25 ~ 5%

1/2 Base
f

Base frequency

0

Voltage

100%

Base frequency

A44 = 00
Constant
Torque

A44 = 01
Variable
Torque

frequency

0

Voltage

100%

Base frequency

A45

20%

frequency