Parameters and Programming

3-9

English

3.2.3 A Group – Advanced Function Parameters

Tunable parameters are indicated with an asterisk ( * ) preceding the parameter
number.

Parameter

Number

Parameter Name/ Description

Min./Max

Range

Units

Factory

Default

Basic Functions

A01

Frequency Command Select
Selects the source of the frequency command for the
drive. Note: If any preset frequency inputs are active, all
other frequency commands will be ignored.
Settings: 00=Frequency pot
01=Input O/OI (Analog reference)
02=Internal frequency (F01 [

FREQUENCY

COMMAND

]/ A20 [

INTERNAL

FREQUENCY

])

00 to 02

Numeric
Value

01

A02

Start Command Select
Selects the source of the start command.
Settings: 01=Control terminal block
02=Start Key (Input from Start Key on drive
keypad)

01 to 02

Numeric
Value

01

A03

Base Frequency
Set value to rated nameplate frequency of motor

50 to 360

1 Hz

60

A04

Maximum Frequency
Highest frequency the drive will output.
Note: If a maximum frequency less than A03 [

BASE

FREQUENCY

] is needed, use A61 [

UPPER

FREQUENCY

LIMIT

]. Refer to diagram in A03 [

BASE

FREQUENCY

].

50 to 360

1Hz

60

Analog input reference adjustment

A11

Analog Frequency Minimum
Sets the frequency that corresponds to a 0V or 4mA
analog signal.

0.0 to 360.0

0.1 Hz

0.0

A12

Analog Frequency Maximum
Sets the frequency that corresponds to a 10V or 20mA
analog signal. A value of 0.0 will disable this function.
Refer to diagram in A11 [

ANALOG

FREQUENCY

MINIMUM

].

0.0 to 360.0

0.1 Hz

0.0

100%

Base
Frequency
A03

0

Start

Frequency
b82

Maximum
Frequency
A04

Frequency

Voltage

Command
Frequency

Hz

Minimum
Frequency
A62

Upper
Frequency Limit
A61

A12

A13

0V
4mA

A14

10V
20mA

% Input
Scale

Frequency

A11