Create a devicenet scanlist, Create a, Devicenet – Rockwell Automation 1769-L3xx CompactLogix System Quick Start User Manual

Page 150: Scanlist, Devicenet only

Advertising
background image

150

Publication IASIMP-QS001C-EN-P - October 2009

Chapter 12 Create a PowerFlex 70 Application

Create a DeviceNet Scanlist

DeviceNet only

1. Move the controller keyswitch to

PROG and go offline.

2. In RSLogix controller organizer,

right-click the 1769-SDN and select
Properties.

3. On the RSNetWorx tab, click

the RSNetWorx icon.

4. In RSNetWorx for

DeviceNet, click Who Active to go
online.

5. Click OK.

If the drive does not display or
displays with an error regarding the
EDS file, see Knowledgebase article
20539.

6. Right-click the PowerFlex 70 drive and

select Download to Device.

7. Click Yes.

The configuration is downloaded to
the PowerFlex 70 drive.