Chapter 12 Create a PowerFlex 70 Application
Create a DeviceNet Scanlist
DeviceNet only
1. Move the controller keyswitch to
PROG and go offline.
2. In RSLogix controller organizer,
right-click the 1769-SDN and select
Properties.
3. On the RSNetWorx tab, click
the RSNetWorx icon.
4. In RSNetWorx for
DeviceNet, click Who Active to go
online.
5. Click OK.
If the drive does not display or
displays with an error regarding the
EDS file, see Knowledgebase article
20539.
6. Right-click the PowerFlex 70 drive and
select Download to Device.
7. Click Yes.
The configuration is downloaded to
the PowerFlex 70 drive.