Publication IASIMP-QS001C-EN-P - October 2009

Chapter 13 Create a PowerFlex 40 Application

EtherNet/IP, ControlNet, and DeviceNet

Use the reference on

page 181

to make the following parameter value edits on your

PowerFlex 40.

1. If your PowerFlex 40 has been previously used, reset it to factory defaults.

a. Change the value of parameter P041 from 0 to 1.

The drive is reset and fault F048 is displayed and blinks.

b. Press

to clear the fault.

c. Press

to return to editing parameters.

2. Change the value of parameters P036 and P038 from 0 to 5.

Changing these parameters switch control the Start Source and the Speed Reference
from the keypad to the communication port, giving you the ability to control these
functions from the RSLogix 5000 tags.

3. Press

to accept parameter edits.

For EtherNet and ControlNet networks, go to

Test the PowerFlex 40 Tags on page 183

.

For a DeviceNet network, go to

Test the PowerFlex 40 Tags on page 185

.