Configure the communication adapter, Configure the, Communication – Rockwell Automation 1769-L3xx CompactLogix System Quick Start User Manual

Page 66: Adapter

Advertising
background image

66

Publication IASIMP-QS001C-EN-P - October 2009

Chapter 5 Prepare the PowerFlex 40 Drive

Configure the Communication Adapter

Adapter

Action

Figure

EtherNet/IP
22-COMM-E

The Ethernet address (MAC) is found on
the adapter’s label. Record the Ethernet
address (MAC) on the

Network

Worksheet

. This address is used to set

the IP address.

For example:

ControlNet
22-COMM-C

Set the adapter’s node address.

This example uses node number 3.

Important: The front side of the adapter
(shown here) faces down when it is
installed in the drive. So, in the installed
position, port A is to the right of port B.

DeviceNet
22-COMM-D

1. Set the adapter’s node address.

This example uses node number 3.

2. Set the rate to Autobaud.

HW Address 00:00:BC:21:D7:BE

2

1

0

9

8

3

4

5

6

7

2

1

0

9

8

3

4

5

6

7

Tens Digit

Ones Digit

A

B

Node 3 shown

Node

Switch

1

2

3

4

5

6

0

0

0

0

0

0

0

1

1

0

0

0

0

0

2

0

1

0

0

0

0

3

1

1

0

0

0

0

4

0

0

1

0

0

0

5

1

0

1

0

0

0

6

0

1

1

0

0

0

Rate

Switch

7

8

125 Kbps

0

0

250 Kbps

1

0

500 Kbps

0

1

Autobaud

1

1

2

1

8

3 4 5 6 7

NODE

RATE

2

1

8

3 4 5 6 7

Up = 1 =
Down = 0 =

Node 3 Shown
Autobaud Shown