Test the powerflex 70 tags, Devicenet only – Rockwell Automation 1769-L3xx CompactLogix System Quick Start User Manual

Page 163

Advertising
background image

Publication IASIMP-QS001C-EN-P - October 2009

163

Create a PowerFlex 70 Application Chapter 12

Test the PowerFlex 70 Tags

DeviceNet only

TIP

To change a tag in RSLogix:

1. Select the tag value.
2. Enter or select the desired value.
3. Press Enter.

2. In the controller organizer, double-click

Controller Tags.

If you have added distributed I/O to your
project in

Chapter 11

, skip to

step 4

.

3. Change the tag

O.CommandRegister.Run tag
to 1.

This changes the 1769-SDN
scanner to Run mode.

4. At the tag O.Reference, change

the value to 15000 engineering
units (this is approximately 59.5
Hz).

This is the speed your drive will
accelerate to and is determined
using the equation shown.

1. Move the controller keyswitch to RUN.

EU

Hz

--------

32767

130

---------------

=

PowerFlex 70 tags are identified
in the description column.