Rockwell Automation AADvance Controller System Build User Manual

Page 107

Advertising
background image


Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:

4-27

The resource and IP Address dialog box opens.

6)

Enter the resource value into the Resource Number field, click Apply.

Returning to the main window of the utility, the controller status will show
Pending Restart.

7)

To complete the update, cycle the power to the controller.

8)

Refresh the screen to confirm that the new resource number is displayed in the

resource field and the controller status is configurable.

The Resource Number must also be configured in the application, in the
Resource Properties.

Configure the IP Address in the Controller

Configure the IP Address in the Controller

Configure the IP Address in the Controller

Configure the IP Address in the Controller

When you build a new AADvance controller, or install a new 9100 processor base
unit, you have to configure the IP Address stored in the controller.

The procedure to configure the IP Address uses the AADvanceDiscover utility.
Changes take effect immediately and you do not have to restart the controller. To set
the IP Address do the following:

1)

Make a note of the controller's MAC address (Controller ID); this is shown on a

label on the processor base unit. Install at least one 9110 processor module into
the processor base unit.

Advertising