ControlFLASH will launch and you can now upgrade the Processor Module
firmware.

Upgrade the Processor Module Recovery Mo

Upgrade the Processor Module Recovery Mo

Upgrade the Processor Module Recovery Mo

Upgrade the Processor Module Recovery Mode Firmware

de Firmware

de Firmware

de Firmware

This is the recommended procedure to upgrade the processor module firmware using
the ControlFLASH Utility.

Note: ControlFLASH can upgrade 3 processor modules at once when installed into a
9100 base unit and they are in the Recovery Mode. To do this press and hold the
Fault Reset button on all three processors when they are being powered up during a
power on/off cycle until the AUX LED goes Amber.

WARNING

FIRMWARE UPGRADE DANGER TO A RUNNING SYSTEM

Do not attempt to upgrade firmware on a running system. Control
FLASH will not warn you that a system is running and you will lose
control of the application when the system reboots.

1)

Run the ControlFLASH software by either:

Launching from the installation

Double clicking the desktop icon

Launching from the Start button