Rockwell Automation AADvance Controller System Build User Manual

Page 79

Advertising
background image


Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:

3-35

Force

Provides an indication that variables are being locked/forced by the
application. The same indication will show for all educated and
synchronised processors

OFF

No power and stays off while the module is booting up (10 to 20 seconds)

GREEN

No variables are being locked/forced

AMBER

Module is in the Recovery Mode.

or

an operating controller has at least one variable being locked/forced

Aux

This LED is controlled by the application. The application can turn it on/off
and any colour except when the processor is in the Recovery Mode and
the application is stopped

OFF

No power and stays off while the module is booting up (10 to 20
seconds), or under application control

GREEN

Under application control

AMBER

Module is in the Recovery Mode

or

under application control

Serial 1 and 2

Provides an indication of serial port activity

OFF

No power and stays off while the module is booting up (10 to 20 seconds)

RED

Pulse stretched Tx

GREEN

Pulse stretched Rx

AMBER

Tx and Rx activity in close proximity

Ethernet 1 and 2

Provides an indication of Ethernet port activity

OFF

No power and stays off while the module is booting up (10 to 20 seconds)

GREEN

Ethernet link present

AMBER

Tx or Rx activity

Note: When inserting more than one processor module they MUST be inserted one
at a time and the module allowed to educate (in the case of a 2nd and 3rd processor).