background image

1-8

Document: 553632

(ICSTT-RM448_EN_P) Issue: 08:

System Build Manual (AADvance Controller)


Physical Features

Physical Features

Physical Features

Physical Features

An innovative feature of the AADvance controller is the design of the hardware.
Everything fits together easily without any need for inter-module wiring.

Environmental Specification

Environmental Specification

Environmental Specification

Environmental Specification

The following environmental specification defines the minimum recommended
environmental conditions for an AADvance controller installation. Additional
conditions apply to installations in a Hazardous environment.

Table 1:

Table 1:

Table 1:

Table 1:

Environmental Specification

Environmental Specification

Environmental Specification

Environmental Specification

Attribute

Value

Operating Temperature Range:
For use in a Hazardous Environments (see
UL508 certification)
Processor Modules
I/O Modules and Assemblies

For use in Non-hazardous environments (see
TUV Certification)
Processor Modules, I/O modules and
Assemblies




–25 °C to 60 °C (–13 °F to 140 °F)
–25 °C to 70 °C (–13 °F to 158 °F)



–25 °C to 70 °C (–13 °F to 158 °F)

Storage and Transport Temperature

–40 °C to 85 °C (–40 °F to 185 °F)

Module Surface Temperature (during normal
operation)

43° C (109 °F) ± 2 °C

Humidity

Operating

10% to 95% RH, non-condensing

Storage and Transport

10% to 95% RH, non-condensing

Vibration

Functional Stress

5Hz to 9Hz

Continuous

1.7mm amplitude

Occasional

3.5mm amplitude

Withstand

10Hz to 150Hz

Acceleration

0.1g in 3 axes

Endurance

10Hz to 150Hz

Acceleration

0.5g in 3 axes

Shock

15g peak, 11ms duration, ½ sine

Altitude

Advertising