The suggested values for R1 and R2 are as follows:

R1 = 15K Ω 1%, 1W (maximum power dissipated is 47mW at 26.4V)

R2 = 3K9 Ω 1%, 1W (maximum power dissipated is 182mW at 26.4V)

Suggested threshold values for both of the above circuits are as follows:

Threshold ID

Value (mV)

Maximum Allowed

=

32000

SHORT CIRCUIT

Threshold 8

=

19000

Threshold 7

=

18500

ON (nominal 16V)

Threshold 6

=

11000

Threshold 5

=

10500

INDETERMINATE

Threshold 4

=

6500

Threshold 3

=

6000

OFF (nominal 8V)

Threshold 2

=

3500

Threshold 1

=

3000

OPEN CIRCUIT

Assumptions:

Loop supply voltage = 24V ± 10%

Maximum Field Cable Line Resistance: < 100 Ω total; this means < 50 + 50 Ω for
the two cables.

Minimum Isolation is 0.75M Ω between the field loop conductors.

These values will allow the input to detect more accurately different voltage levels
that represent OPEN CCT - OFF - ON - SHORT CCT and will also detect Over
Voltage and an input which is neither ON or OFF. The values ensure that a line
fault will be declared before it becomes possible for a false declaration of On and
Off states due to a combination of resistor value drift and loop voltage variation.
The F&G circuit will also allow two devices to be in alarm without reporting short
circuit.

All of the input circuits are suitable for simplex, dual and TMR configurations.

The F&G circuit assumes that the devices are volt-free contacts.

For further information, please refer to application note AN-T90001 Field Loop
Configuration. This also includes advice for fire detectors which are not simple volt
free contacts.