Allocations of Coding Pegs

Allocations of Coding Pegs

Allocations of Coding Pegs

Allocations of Coding Pegs

Coding pegs are assigned to each module type as shown in the following table:

Application

Key A

Key B

Key C

9100 processor base unit
(for 9110 processor module)

1

1

1

9801/2/3 digital input termination assemblies
(for digital input modules)

2

1

1

9831/2/3 analogue input termination assemblies
(for analogue input modules)

2

1

3

9851/2 digital output termination assemblies
(for digital output modules)

3

1

1

9842/1 analogue output module

3

1

2

This example shows pins set to positions 2, 1, 1 for a 9401 digital input module.

Install Base Units and Ter

Install Base Units and Ter

Install Base Units and Ter

Install Base Units and Termination Assemblies: Flat Panel Assembly

mination Assemblies: Flat Panel Assembly

mination Assemblies: Flat Panel Assembly

mination Assemblies: Flat Panel Assembly

Flat panel assembly secures the AADvance controller directly onto a panel, without
the use of DIN rails. Do the following:

1)

The base units carry latches which are intended to secure the base units to DIN

rails.

2)

Assemble the base units. Place the base units on a workbench and use the

backplane clips (supplied) to join adjacent base units together.