Rockwell Automation AADvance Controller System Build User Manual

Page 76

Advertising
background image

3-32

Document: 553632

(ICSTT-RM448_EN_P) Issue: 08:

System Build Manual (AADvance Controller)


Fault Reporting Reference Information

Fault Reporting Reference Information

Fault Reporting Reference Information

Fault Reporting Reference Information

Each module has a set of front panel status indicators. The purpose and meaning of
these indicators relevant to each module is as follows:

Status Indicators on the T94xx Series Input and Output Module

Status Indicators on the T94xx Series Input and Output Module

Status Indicators on the T94xx Series Input and Output Module

Status Indicators on the T94xx Series Input and Output Module

Table 6:

Table 6:

Table 6:

Table 6:

Status Indicators on the 94xx Series Input and Output Module

Status Indicators on the 94xx Series Input and Output Module

Status Indicators on the 94xx Series Input and Output Module

Status Indicators on the 94xx Series Input and Output Module

Indicator

Status

Description

Healthy

Provides an indication of the general status of the module

OFF

No power

GREEN

No module faults present

RED

One or more module faults are present

Note.

1. The Healthy indicator may turn RED immediately upon application of
power to the module, before then turning GREEN

2. If Healthy is GREEN and the Ready and Run are RED then the
module is said to be in its "shutdown state" refer to the Troubleshooting
Manual - Chap 3 for more information on the shutdown state.

Ready

Provides an indication of the module's ability to report channel values to a
running application

OFF

No power or unlocked

GREEN

Locked and ready to report channel values

RED

Locked but not ready to report channel values

Run

Provides an indication that the module is reporting channel values to a
running application

OFF

No power or unlocked

Advertising