Rockwell Automation AADvance Controller System Build User Manual

Page 126

Advertising
background image

8-8

Document: 553632

(ICSTT-RM448_EN_P) Issue: 08:

System Build Manual (AADvance Controller)


SFF

SFF

SFF

SFF

Safe Failure Fraction. Given by (the sum of
the rate of safe failures plus the rate of
detected dangerous failures) divided by (the
sum of the rate of safe failures plus the rate
of detected and undetected dangerous
failures).

SIF

SIF

SIF

SIF

Safety Instrumented Function. A form of
process control that performs specified
functions to achieve or maintain a safe state
of a process when unacceptable or
dangerous process conditions are detected.

SIL

SIL

SIL

SIL

Safety Integrity Level. One of four possible
discrete levels, defined in IEC 61508 and IEC
61511, for specifying the safety integrity
requirements of the safety functions to be
allocated to a safety-related system. SIL4 has
the highest level of safety integrity; SIL1 has
the lowest.
The whole of an installation (of which the
AADvance system forms a part) must meet
these requirements in order to achieve an
overall SIL rating.

SNCP

SNCP

SNCP

SNCP

SNCP (Safety Network Control Protocol) is
the Safety Protocol that allows elements of
an AADvance System to exchange data.
SNCP is a SIL 3 certified protocol which
provides a safety layer for the Ethernet
network making it a "Black Channel".

SNTP

SNTP

SNTP

SNTP

Simple Network Time Protocol. Used for
synchronizing the clocks of computer
systems over packet-switched, variable-
latency data networks.

structured text

structured text

structured text

structured text

A high level IEC 61131-3 language with
syntax similar to Pascal. Used mainly to
implement complex procedures that cannot
be expressed easily with graphical languages.

synchronous

synchronous

synchronous

synchronous

A data communications term describing a
serial transmission protocol. A pre-arranged
number of bits is expected to be sent across
a line per second. To synchronise the
sending and receiving machines, a clocking
signal is sent by the transmitting computer.
There are no start or stop bits.

T

T

T

T

TA

TA

TA

TA

See 'termination assembly'.

target

target

target

target

An attribute of a 'configuration' which
describes characteristics of the AADvance
controller on which the configuration will
run. Includes characteristics such as the
memory model and the sizes of variable
types for the controller.

TCP

TCP

TCP

TCP

Transmission control protocol. One of the
core protocols of the Internet Protocol
suite. It provides reliable, ordered delivery
of a stream of bytes from a program on one
computer to another program on another
computer. Common applications include the
World Wide Web, e-mail and file transfer
and, for an AADvance controller, Modbus
communications over Ethernet.

termination assembly

termination assembly

termination assembly

termination assembly

A printed circuit board which connects field
wiring to an input or output module. The
circuit includes fuses for field circuits. The
board carries screw terminals to connect
field wiring to the controller, and the whole
assembly clips onto the 9300 I/O base unit.

TMR

TMR

TMR

TMR

Triple modular redundant. A fault tolerant
arrangement in which three systems carry
out a process and their result is processed
by a voting system to produce a single
output.

TÜV cert

TÜV cert

TÜV cert

TÜV certification

ification

ification

ification

Independent third party certification against
a defined range of international standards
including IEC 61508.

Advertising