Procedure to Connect Serial Communications Cabling

re to Connect Serial Communications Cabling

re to Connect Serial Communications Cabling

re to Connect Serial Communications Cabling

Connect the serial communications cabling to the six plugs labelled S1-1 through S3-2
on the T9100 processor base unit.

For each serial communications connection, connect the cabling according to the
following illustration.

Apply a minimum tightening torque of 0.22Nm (0.16ft lb) to the terminal screws.

Make sure the length of the cable does not exceed 1,200m (3,900ft).

Note: The line functions shown in this table ("receive" and "transmit") are with
respect to the processor base unit.

Terminal

Function Description (4-wire)

Function Description (2-
wire)

TRX_A

Receive data A (inverting)

Transmit/receive data A
(inverting)

TRX_B

Receive data B (non-inverting)

Transmit/receive data B (non-
inverting)

0V

Instrument ground (signal ground)

Instrument ground

TX_B

Transmit data B (non-inverting)

not used

TX_A

Transmit data A (inverting)

not used

To connect to the external communication link you should terminate the receive end
of the link.