Rockwell Automation AADvance Controller System Build User Manual

Page 87

Advertising
background image


Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:

4-7

Step Task

When the Run indicator goes AMBER press the Fault Reset button and the processor will display the
following indications:

2.

Healthy

Green

Ready

GREEN (can flash for a short time as the module educates)

Run

AMBER to GREEN (AMBER as the module educates)

System Healthy

GREEN

Force

Off to GREEN

Aux

Off (application dependent)

Serial 1

Dependent on Data Connection

Serial 2

Dependent on Data Connection

Ethernet 1

Dependent on Data Connection

Ethernet 2

Dependent on Data Connection

3.

To insert a 3rd processor module repeat step 1 and insert in Slot C.

I/O Module Start Up Process

I/O Module Start Up Process

I/O Module Start Up Process

I/O Module Start Up Process

To start up an Input/Output Module follow this procedure:

Note: The start up sequence is different when a module is installed into an on-line
system that is running compared to installing the module into a system that is off-line
and has processor modules but no I/O modules installed. The first part of this
procedure covers the initial start up of an off-line system, the second part covers a
system that is on line and you are adding I/O modules.

Table 10:

Table 10:

Table 10:

Table 10:

Single

Single

Single

Single Module or First Module of a group Installation Procedure

Module or First Module of a group Installation Procedure

Module or First Module of a group Installation Procedure

Module or First Module of a group Installation Procedure

Step

Task

1.

This procedure applies to a single module installed or the first module of a redundant group.

2

Install the Input/Output Module and turn the locking screw to the lock position.

3.

The input module will provide the following status indications:

Healthy

GREEN

Ready

RED

Run

RED

Channel 1 – 8

Off

4.

The input module will enter its start up sequence during which the module will educate.
Wait for approximately 3 seconds.

5.

The module will now provide the following status indications:

Healthy

GREEN

Advertising