Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:

4-5

Step Task

Force

Will remain OFF as the Module boots up (10 to 20 seconds) then stays
OFF until the module has educated.

Aux

Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection.

Serial 1

Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection

Serial 2

Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection

Ethernet 1

Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection

Ethernet 2

Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection

You have to set up the processor IP Address so that the workstation can communicate with the
processor module and download the latest firmware build and configure the processor variables.

3.

Set the Controller IP Address for all the processor modules using the "AADvance Discover
Utility". (Refer to the Configuration Guide for detailed instructions on using the AADvance
Discover Utility Doc. No: 553633).

4.

Install a Program Enable Key. Download a valid application and press the FAULT RESET
button. When the application is downloaded and valid the module will display the following
indications:

Valid Application Downloaded

Healthy

GREEN

Ready

GREEN

Run

RED to GREEN (Flashes GREEN as the module educates)

System Healthy GREEN

Force

GREEN

Aux

Off (Application Dependent)

Serial 1

Dependent on data connection

Serial 2

Dependent on data connection

Ethernet 1

Dependent on data connection

Ethernet 2

Dependent on data connection