For each power supply connection, do the following:

Connect the negative line from the power supply, typically labelled '0V', to the left-
hand terminal.

Connect the positive line from the power supply, typically labelled '+24V', to the
right-hand terminal.

Apply a minimum tightening torque of 0.5 Nm (0.37 ft lb) to the terminal screws.

Note: Make sure that PWR-1 and PWR-2 are supplied from independent 24V dc
sources.

Refer to the illustration for an example.