Operating
0 to 2000m (0 to 6,600 ft.)
Storage and Transport
0 to 3000m (0 to 10,000 ft.)
This equipment must not be transported in
unpressurized aircraft flown above 10,000 ft.
Electromagnetic Interference
Tested to the following standards: EN 61326-
1:2006, Class A; EN 61326-3-1:2008, EN 54-4:
1997, A1; EN 61131-2:2007; EN 62061:2005.
Hazardous Location Capability
Suitable for Class I Div 2 Groups A, B, C and
D
Note:
Casing: Standard AADvance modules also have a plastic casing and are rated IP20:
Protected against solid objects over 12mm (1/2in.) for example "fingers".There is no
specific protection against liquids.