4-8

Document: 553632

(ICSTT-RM448_EN_P) Issue: 08:

System Build Manual (AADvance Controller)


Ready

GREEN

Run

AMBER

Channel 1 – 8

Off

6.

Press the Fault Reset button on the processor module and the Run indication goes GREEN.

7.

The module will now be on-line with the following status indications:

Healthy

GREEN

Ready

GREEN

Run

GREEN

Channel 1 – 8)

Dependent on channel status

8.

If the module fails to educate and go on-line replace the module.

Table 11:

Table 11:

Table 11:

Table 11:

Second or third Module of a Group Installation Procedure

Second or third Module of a Group Installation Procedure

Second or third Module of a Group Installation Procedure

Second or third Module of a Group Installation Procedure

Step

Task

1.

This procedure applies to a second or third module of a redundant group.

2

Install the Input/Output Module and turn the locking screw to the lock position.

3.

The input module will provide the following status indications:

Healthy

GREEN

Ready

RED

Run

RED

Channel 1 – 8

Off

4.

The input module will enter its start up sequence during which the module will educate.
Wait for approximately 3 seconds.

5.

The module will now provide the following status indications:

Healthy

GREEN

Ready

GREEN

Run

AMBER

Channel 1 – 8

Off

6.

Press the Fault Reset button on the processor module and the Run indication goes GREEN.

7.

The module will now be on-line with the following status indications:

Healthy

GREEN

Ready

GREEN

Run

GREEN

Channel 1 – 8)

Dependent on channel status