Rockwell Automation AADvance Controller System Build User Manual

Page 69

Advertising
background image


Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:

3-25

3)

The module locking screw requires a quarter turn clockwise to lock. Use a broad

(9mm) flat blade screwdriver to lock the locking screw.

Note: The locking screw acts as a power interlock device. Therefore, the locking
screw must be in the locked position after the power is applied otherwise the module
will not boot up.

Upgrade a Processor Module Firmware

Upgrade a Processor Module Firmware

Upgrade a Processor Module Firmware

Upgrade a Processor Module Firmware

To upgrade ethe firmware use the Recovery Mode and follow the procedures using
the ControlFLASH utility. Refer to the configuration Guide for detailed procedures on
using the ControlFLASH utility.

Note: If you need to downgrade the firmware to meet the requirements of your
application and system contact Product support.

Install a Processor Back

Install a Processor Back

Install a Processor Back

Install a Processor Back----up Battery

up Battery

up Battery

up Battery

The T9110 processor module uses a battery to support its internal clock and memory
when it is powered off. The battery condition is monitored by the module diagnostics
every 24 hours. If the battery voltage is low, an application variable is set indicating
there is a problem and the processor Healthy LED goes red.

Note: The processor back up battery is supplied separately and must be installed into
each new processor.

To install a new battery, do the following: