Power and External Connector Wiring Details

Power and External Connector Wiring Details

Power and External Connector Wiring Details

Power and External Connector Wiring Details

External connectors for power, serial data, Ethernet data and the application security
device are connected to the T9100 Processor base unit. The field connections for I/O
data are connected to the Termination Assemblies.

The wiring specifications are as follows:

Table 5:

Table 5:

Table 5:

Table 5:

Exte

Exte

Exte

External Connectors

rnal Connectors

rnal Connectors

rnal Connectors

Connector
Function

Location

Designation

Summary
Specifications

Remarks

Controller power in T9100

processor
base unit

PWR–1,

PWR–2

Two 3-way connectors

Conductor cross section
maximum 3.3mm² (12
AWG)

Stripping length
7mm (9/32 in.)

Wire to screw terminals on
free connectors supplied with
processor base unit

Serial ports

T9100
processor
base unit

S1–1, S1–2

S2–1, S2–2

S3–1, S3–2

Six 5-way connectors

Conductor cross section
maximum 1.31mm² (16
AWG)

Stripping length
7mm (9/32 in.)

Wire to screw terminals on
free connectors supplied with
processor base unit

Ethernet ports

T9100
processor
base unit

E1–1, E1–2

E2–1, E2–2

E3–1, E3–2

RJ45 socket

Use network patch cords (not
supplied)

Field wiring (sensors,
actuators and field
power sources)

I/O
Termination
Assemblies

None

Screw terminal blocks

Conductor cross section
maximum 1.31mm² (16
AWG)

Stripping length
6mm (¼ in.)

Wire to screw terminal
blocks on termination
assemblies

Program enable key

T9100
processor
base unit

KEY

DB9 Plug with detected
circuit

Removable security device
that allows workbench
programming, variable
locking/forcing and AADvance
Discover write access.
Supplied with base unit

Conductor cross sections specified are for stranded and solid conductors, with and
without a ferrule.

Note: The AADvance controller does not provide mechanical support to hold power
or external communications. Mechanical support should be arranged in the design of
the installation, for example through the provision of suitable cable trunking.