Rockwell Automation AADvance Controller System Build User Manual
Page 50
Advertising
![background image](/manuals/581463/50/background.png)
3-6
Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:
System Build Manual (AADvance Controller)
Allocations of
Allocations of
Allocations of
Allocations of Coding Pegs
Coding Pegs
Coding Pegs
Coding Pegs
Coding pegs are assigned to each module type as shown in the following table:
Application
Key A
Key B
Key C
9100 processor base unit
(for 9110 processor module)
1
1
1
9801/2/3 digital input termination assemblies
(for digital input modules)
2
1
1
9831/2/3 analogue input termination assemblies
(for analogue input modules)
2
1
3
9851/2 digital output termination assemblies
(for digital output modules)
3
1
1
9842/1 analogue output module
3
1
2
This example shows pins set to positions 2, 1, 1 for a 9401 digital input module.