Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:

4-19

10)

Click OK and another error message is displayed.

11)

Click OK then Cancel to Exit ControlFLASH.

12)

Reboot the processor module by switching the power OFF then ON and hold in

the Fault Reset button as the module reboots until the Aux LED goes amber.

The processor module(s) will reboot into the Recovery Mode indicated by the
following LED states on the processor module.

Healthy

Green (dependent on Module health)

Ready

Amber

Run

Amber

System Health

Green (dependent on system health)

Force

Amber

Aux

Amber

Stage 2: Installing the ControlFLASH Firmware Kit for OS, FPGA, LSP and BUSP

Stage 2: Installing the ControlFLASH Firmware Kit for OS, FPGA, LSP and BUSP

Stage 2: Installing the ControlFLASH Firmware Kit for OS, FPGA, LSP and BUSP

Stage 2: Installing the ControlFLASH Firmware Kit for OS, FPGA, LSP and BUSP

This procedure describes how to upgrade the Processor Firmware for OS, FPGA, LSP
and BUSP.

The procedure that follows is basically the same as for stage 1.

1)

Run the 354400_102_ControlFLASH.msi file.

2)

Click NEXT.

3)

Read and agree the License.

4)

Click Browse to select the location of the installation or Next to choose the

default location.

5)

Click Next to confirm the installation.

ControlFLASH installs and shows the progress bar.

6)

Click Yes I want to launch ControlFLASH, then click Close.