Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:

3-27

4)

To control the time setting, wire variables to the RTC Control points:

RTC Write

RTC Read

5)

Wire Variables to RTC Control:

Hours

Minutes

Seconds

6)

Set RTC Read to be always True (the time will not be written unless this point is

also True).

7)

Set RTC Control elements Hours, Minutes and Seconds to be always True.

8)

Use an external trigger to change RTC Write from False to True at the time you

have preset in step 3.

The time will now be set into Real Time Clock

Note: On the very first setting it will be necessary to program all the time elements
(Year, Month, Day etc)

Install I/O Modules

Install I/O Modules

Install I/O Modules

Install I/O Modules

Inspect the module:

Before inserting a new I/O module, inspect it for damage.

The identification labels on the sides of the I/O module will be hidden once the
module is installed. Therefore before installation record the location of the module
and the details shown on the label.

Examine the coding pegs on the termination assembly and verify they complement
the sockets on the rear of the new I/O module.

To install each I/O module, do the following:

1)

Examine the coding pegs on the termination assembly and verify they complement

the sockets on the rear of the I/O module.

2)

Place the I/O module on to the dowel pins on the T9300 I/O base unit. Make sure

the slot on the head of the module clamp screw is vertical and then push the
module home until the module connectors are fully mated with the I/O base unit
and termination assembly connectors.

3)

The locking screw requires a quarter turn clockwise to lock. Use a broad (9mm)

flat blade screwdriver to lock the clamp screw.

Note: The locking screw acts acts as a power interlock device and must be in the
locked position when power is applied otherwise the module will not power up.