Chapter 4: Testing and troubleshooting

96

Concord 4 Installation Manual

Testing the system

Before testing, we recommend that you close the panel cabinet door and the
covers on all modules (mounted outside the cabinet.) The testing environment
should match the system working environment.

You should test the system after installation or service and after adding or
removing devices from the system. See “Cellular backup communication” on
page 104 if you do not achieve correct test results.

Testing the system includes:

• “Basic system commands” below
• “Zones/sensors” on page 97
• “Phone communication” on page 98
• “Central station/pager communication” on page 99
• “Outputs and sirens” on page 100
• “Light control” on page 101
• “Energy saver module (ESM)” on page 101
• “Fixed display LCD touchpad chime and trouble beep tones” on page 102
• “Audio verification module communication” on page 103
• “Cellular backup communication” on page 104

Basic system commands

Table 14 below describes basic touchpad operating commands. For complete
details on system operation, including user programming, refer to the Concord 4
User Manual.

Table 14: Basic touchpad commands

Command

System response

* (STATUS)

Indicates current system status

*, *

Indicates AC power, battery, and current system status

1, code

Disarms system to OFF

2, code

Arms system to STAY

2 (quick arm on)

Arms system to STAY

3 (quick arm on)

Arms system to AWAY

2 or 3, code, 4
or
2 or 3, 4

Arm system

—no delay (no exit or entry delay)

5, 2 or 3, code
or
5, 2 or 3

Arms system silently (no arming status beeps