Chapter 4: Testing and troubleshooting

Concord 4 Installation Manual

109

• The installer code is being used to disarm the system. The system is

designed not to disarm using the installer code. Use a regular or system
master code to disarm the system.

Bypassing issues

Touchpad indicates Invalid and/or “Invalid” is heard when you attempt to
bypass a sensor.

• You may be attempting to bypass a 24-hour sensor that cannot be bypassed

(group 26 fire sensors).

• The sensor is not active in the current arming level.

• Arm the system to the desired arming level, then bypass.

System cancels sensor bypass when you try to arm to Level 2 or 3.

Sensor is being bypassed before arming to Level 2 stay or Level 3 away. Arm to
the desired level before bypassing a sensor.

Wireless sensor and touchpad battery issues

System indicates Sensor/Touchpad nn low battery.

Replace the indicated device battery and test the sensor/touchpad after replacing
the battery.

Central station/pager reporting issues

Trouble with your central station or pager.

Check the programming, panel connections, and proper phone line with line
seizure.

To check your programming:

1. Make sure you enter the correct phone number.

2. Make sure you enter the correct account number.

3. Check that the appropriate format is chosen (SIA or CID).

4. Make sure the appropriate reports are turned on.

To check your panel connections:

1. Concord panels are polarity sensitive, so check for proper polarity:

The positive green lead or (TIP) wires must connect to terminal 25 on the
board.